Technical FAQs

Ask a Question

What is the Modbus TCP explicit messaging feature of BMENOP0300 ?

The BMENOP0300 module presents the following Modbus TCP explicit messaging features:
 
Feature
Capacity
Client
 
maximum number of simultaneous connections
16 connections
maximum number of concurrent requests
16 requests
Server
 
maximum number of concurrent requests
12 requests
maximum number of simultaneous connections
32 connections
Maximum Message Size
 
read
250 bytes (125 words) excluding header
write
240 bytes (120 words) excluding header  