The Varplus logic Displays "I Lo ALARM".What action to be taken?

The cause may be due to that  the measured current is to small (< 15 mA)

The action to be take:
  • Check connection of CT
  • CT ratio is too high compared to real current
  • Remove short circuit link of the CT