  • Main
    range of product
    INF100...160
    range
    Fupact
    product name
    Fupact INF
    device short name
    INFD160
    product or component type
    Switch-disconnector-fuse
    device application
    Protection
    poles description
    3P
    protected poles description
    3f
    fuse type
    DIN
    fuse size
    NH00
    NH000
    network type
    AC
    DC
    network frequency
    50/60 Hz
    Complementary
    control type
    Without handle
    rotary handle mounting location
    Lateral
    rotary handle mounting style
    Extended
    mounting support
    Mounting plate
    DIN rail with specific accessories
    [Ie] rated operational current
    DC-22A : 160 A DC 125 V 2 poles in series
    AC-22A : 160 A AC 50/60 Hz 440/480 V
    AC-22A : 160 A AC 50/60 Hz 660/690 V
    AC-22A : 160 A AC 50/60 Hz 220/240 V
    AC-22A : 160 A AC 50/60 Hz 380/415 V
    AC-23A : 160 A AC 50/60 Hz 440/480 V
    AC-23A : 160 A AC 50/60 Hz 380/415 V
    AC-22A : 160 A AC 50/60 Hz 500/525 V
    AC-23A : 160 A AC 50/60 Hz 500/525 V
    AC-23A : 160 A AC 50/60 Hz 220/240 V
    DC-23A : 160 A DC 250 V 2 poles in series
    DC-23A : 160 A DC 125 V 2 poles in series
    DC-23A : 100 A DC 500 V 4 poles in series
    DC-22A : 160 A DC 250 V 2 poles in series
    DC-22A : 100 A DC 500 V 4 poles in series
    AC-23B : 160 A AC 50/60 Hz 660/690 V
    [Ith] conventional free air thermal current
    103 A ( 70 °C ) horizontal
    111 A ( 65 °C ) horizontal
    112 A ( 70 °C ) vertical
    118 A ( 60 °C ) horizontal
    120 A ( 65 °C ) vertical
    126 A ( 55 °C ) horizontal
    128 A ( 60 °C ) vertical
    133 A ( 50 °C ) horizontal
    136 A ( 55 °C ) vertical
    140 A ( 45 °C ) horizontal
    144 A ( 50 °C ) vertical
    148 A ( 40 °C ) horizontal
    152 A ( 45 °C ) vertical
    156 A ( 35 °C ) horizontal
    160 A ( 40 °C ) power dissipation per fuse: 12 W
    160 A ( 40 °C ) vertical
    [Ithe] conventional enclosed thermal current
    135 A ( 40 °C ) / Power dissipation per fuse: 12 W 300 mm x 350 mm x 200 mm
    160 A ( 40 °C ) / Power dissipation per fuse: 10 W 300 mm x 350 mm x 200 mm
    maximum power
    110 kW 500/525 V AC 50/60 Hz
    132 kW 660/690 V AC 50/60 Hz
    45 kW 220/240 V AC 50/60 Hz
    80 kW 380/400 V AC 50/60 Hz
    90 kW 415 V AC 50/60 Hz
    rated duty
    Uninterrupted
    intermittent duty class
    Class 120 - 60 %
    [Ui] rated insulation voltage
    1000 V AC 50/60 Hz
    1000 V DC
    [Uimp] rated impulse withstand voltage
    12 kV
    [Ue] rated operational voltage
    500 V DC
    690 V AC 50/60 Hz
    690 V AC 50/60 Hz AC-20
    690 V DC DC-20
    [Im] rated making and breaking capacity
    Icm 105 kA conforming to DIN 690 V with fuse
    Icm 15 kA 690 V without fuse
    Icm 176 kA conforming to BS 415 V with fuse
    Icm 22 kA 415 V without fuse
    Icm 22 kA 500 V without fuse
    Icm 220 kA conforming to DIN 500 V with fuse
    Icn 100 kA conforming to DIN 500 V with fuse
    Icn 50 kA conforming to DIN 690 V with fuse
    Icn 80 kA conforming to BS 415 V with fuse
    suitability for isolation
    Yes
    contact position indicator
    Yes
    contact operation
    Double-break
    Environment
    mechanical durability
    10000 cycles
    electrical durability
    AC-22A : 1500 cycles 500 V AC 50/60 Hz
    AC-22A : 1500 cycles 690 V AC 50/60 Hz
    AC-23A : 1500 cycles 500 V AC 50/60 Hz
    AC-23A : 1500 cycles 690 V AC 50/60 Hz
    [Icw] rated short-time withstand current
    5 kA ( 1 s )
    0.95 kA ( 30 s )
    1.15 kA ( 20 s )
    2.9 kA ( 3 s )
    design
    Horizontal design
    tightening torque
    Terminal : 15...22 N.m
    height
    140 mm
    width
    180 mm
    depth
    130 mm
    standards
    EN/IEC 60269-1
    EN/IEC 60269-4
    EN/IEC 60947-1
    EN/IEC 60947-3
    EN/IEC 60947-5
    product certifications
    KEMA-KEUR
    IP degree of protection
    IP20 conforming to IEC 60529
    IP65 conforming to IEC 60529
    IK degree of protection
    IK07 conforming to EN 50102
    IK10 conforming to EN 50102
    pollution degree
    3
    ambient air temperature for operation
    -25...70 °C
    ambient air temperature for storage
    -50...85 °C
    Contractual warranty
    Warranty period
    18 months